Cat6 vs Cat7: which cable should you install?
Cat7 sounds like the next step after Cat6, and on paper it is faster. In practice it belongs to a different standard, with different connectors, and in most office installations Cat6a is the cable that delivers what Cat7 promises.
The short version
The Cat6 vs Cat7 question is really a question about standards. Cat6 is defined both by the American TIA standard and by the international ISO/IEC 11801, where it is called Class E. Cat7 exists only in the ISO/IEC standard, as Class F, and is not recognised by TIA. That matters more than it sounds, because a Cat7 channel is specified with its own connectors, GG45 or TERA, and not with the familiar RJ45 plug.
Most cables sold as “Cat7” come with RJ45 plugs. The cable itself may be well shielded, but with RJ45 at both ends the link is not a Class F channel, and in practice it performs no better than a good Cat6a installation. For 10 gigabit over the full distance with RJ45, Cat6a is the category built for it.
- Cat6 Gigabit over 100 metres, 10 gigabit over shorter runs. The standard choice for desks.
- Cat6a 10 gigabit over the full 100 metres, with RJ45. The usual choice for new offices and access points.
- Cat7 An ISO/IEC class with shielded pairs and its own connectors; with RJ45 it loses its point.
- Cat8 For short links in data centres at 25 and 40 gigabit, not for office cabling.
Cat6, Cat6a and Cat7 side by side
| Category | Standard | Bandwidth | Connector | 10 gigabit |
|---|---|---|---|---|
| Cat6 | TIA and ISO/IEC (Class E) | 250 MHz | RJ45 | Shorter runs, roughly up to 55 m |
| Cat6a | TIA and ISO/IEC (Class EA) | 500 MHz | RJ45 | Up to 100 m |
| Cat7 | ISO/IEC only (Class F) | 600 MHz | GG45 or TERA | Up to 100 m, as a full Class F channel |
The distances are per channel, including the patch leads at both ends, and assume the whole link is installed in the same category.
Is a Cat7 cable a waste of money?
Not always, but it rarely buys anything. A short Cat7 patch lead with RJ45 plugs works like any good shielded patch lead. As fixed cabling in the walls it costs more, is stiffer to install, needs shielded sockets and panels with a proper earth, and the active equipment (switches, access points, computers) all uses RJ45. What decides the result is the installation as a whole, measured after it is done.
What we install and why
The category on the reel matters less than the link that is measured at the end.
Cat6a for new work
10 gigabit over the full distance with the connector every device uses, and headroom for multi-gigabit access points.
One category throughout
Cable, sockets, patch panel and patch leads in the same category. A better cable on a weaker panel performs like the panel.
Measured and documented
Every link tested after installation, with a report per port, so you know what the cabling actually does.
Where our work stops
We lay data cabling, terminate it and test every link; building work such as new cable routes through walls, electrical circuits or cooling is done by a building contractor or electrician. The step below is compared in Cat5e vs Cat6 and the step up in Cat6 vs Cat6a. How a link is measured is in Network cable testing, how a plug is wired in RJ45 wiring, and how a whole installation fits together in Cabling and the server rack.
What it connects to
These pages cover the neighbouring part of the same environment.
Questions we get about this
The ones that come up most, answered briefly.
What is the difference between Cat6 and Cat7?
Cat6 is a TIA and ISO/IEC category for 250 MHz with RJ45 plugs. Cat7 is an ISO/IEC-only class for 600 MHz with fully shielded pairs and its own connectors, GG45 or TERA. TIA does not recognise Cat7.
Is Cat7 better than Cat6a?
On paper it has more bandwidth, but only as a complete channel with GG45 or TERA connectors. With RJ45 plugs, which is how most Cat7 cable is sold, it performs no better than Cat6a, which is built for 10 gigabit over 100 metres with RJ45.
Can I use Cat7 patch leads with Cat6 cabling?
Yes, they use the same RJ45 plug and work together, but the link performs at the level of its weakest part. The Cat6 installation decides what you get.
Do you also do the building work for new cable routes?
No. We lay, terminate and test the data cabling and fit the equipment. Building work such as new routes through walls, electrical circuits or cooling is done by a contractor or electrician, and we coordinate with them.