Cat6 vs Cat6a: which cable an office should install now, and when to go fibre
Cat6 vs Cat6a looks like one line in a quote, but that cable will still be in the ceiling after the switches have been replaced three times. This is what the difference means in practice: which speed over which length, what PoE and shielding change, why “Cat7” on the drum does not mean what you think, and when fibre is the better choice.
Cat6 and Cat6a both run 1 Gbit over a hundred metres. The difference is 10 Gbit: Cat6a does it over the full length, Cat6 only over a shorter run and under conditions.
Cat6a is thicker and stiffer, so containment and wall penetrations have to be sized for it. That has to be known before the contractor makes the openings.
“Cat7” with RJ45 plugs is not a Cat7 link under the standard. What counts is the class of the whole link, tested at handover.
Cat6 vs Cat6a: what the difference is in practice
Cat6 is specified up to 250 MHz, Cat6a up to 500 MHz. In the European and international standards (EN 50173 and ISO/IEC 11801) a link built from them is Class E and Class EA. The frequency is not a goal in itself: it sets how much data can pass reliably over a given length.
For 1 Gbit it makes no difference. Both run that over the full hundred metres of a channel: ninety metres of fixed cable from patch panel to outlet, plus no more than ten metres of patch cord in total at both ends.
For 10 Gbit it does. Cat6a is designed for it and runs 10GBASE-T over that full hundred metres. Cat6 only manages it over a shorter run, in the region of fifty-five metres, and even then it depends on how tightly the cables are bundled. That is not a promise you want on a new installation.
What actually has to run over the cable
A desk with a laptop and a dock is well served by 1 Gbit, and will be for a while. The cables that need to go faster are the ones to the access points. Wi-Fi 6, 6E and 7 bring access points with a 2.5 or 5 Gbit uplink, and those speeds (the standard is NBASE-T, or IEEE 802.3bz) were designed precisely to run over existing Cat6, over the full length.
That means two things. If good, tested Cat6 is already in place, that is no reason to rip it out; today’s access points will run on it. And if you are cabling from scratch, Cat6a is the choice that also carries the next generation of access points and 10 Gbit to a meeting room or workshop. The difference in material is small next to the labour; opening up a ceiling is what makes a cable expensive, and how to plan the number of outlets is in our article on cabling and the server rack.
PoE, heat and cable diameter
Access points, cameras and phones take their power over the same cable. With the heaviest PoE standard (IEEE 802.3bt) that reaches several tens of watts per port, and current through a thin conductor gets warm. Bundle a hundred of those cables tightly in a tray and the heat cannot escape, and the cable’s performance drops. The standards include guidance on bundle size for this.
Cat6a often has heavier conductors and a screen that sheds heat better, which is a second argument for Cat6a where a lot of PoE equipment is connected. The trade-off is that the cable itself is thicker and stiffer:
- Fewer fit in a tray or conduit, so containment sized for Cat6 fills up sooner with Cat6a.
- The minimum bend radius is larger, which matters in a shallow comms cabinet and behind a wall outlet.
- Penetrations through walls and floors must be larger. The contractor makes those, so the number and type of cables must be on the table before anyone drills.
U/UTP or shielded: F/UTP, U/FTP and S/FTP
The letter code says what surrounds the cable and what surrounds each pair. U/UTP is unshielded. F/UTP has foil around the whole cable, U/FTP foil around each pair, and S/FTP a braid around the whole plus foil around each pair. Cat6a comes in all of them.
Shielding only works if it is continuous. A shielded system must run unbroken from outlet to patch panel and be bonded to the rack’s earth in the cabinet. A screen that stops halfway or is connected to nothing does not help and can pick up interference itself. If you choose shielded, the earthing of the cabinet belongs in the electrical contractor’s scope.
Unshielded Cat6a works perfectly well in an ordinary office. Shielded is worth considering next to lift motors, machinery and heavy electrical plant, and in a building that is already cabled shielded: do not mix the two in one system.
Cat7 and Cat8: what is on the drum and what the standard says
In the ISO standard Cat7 is cable for Class F, up to 600 MHz. That class was designed for connectors other than RJ45. Put ordinary RJ45 outlets and plugs on it and the link achieves at most what the connector allows: Cat6a. In the American TIA standards Cat7 does not exist at all.
That does not make “Cat7 cable” worthless. It is a sturdy shielded installation cable, and with Cat6a outlets on it you get a perfectly good Cat6a link. But anyone ordering a Cat7 network in the expectation that it goes further than Cat6a will not get that. Ask about the class of the link, not the print on the drum.
Cat8 is a different story: 25 and 40 Gbit over no more than thirty metres, intended for links between switches and servers in a data centre. On the office floor it has no role.
One system, tested at handover
The category of a link is that of its weakest component. Cat6a cable with Cat6 outlets is a Cat6 link, and a cheap patch cord drags a good link down. Cable, outlets and patch panels therefore belong to one system of the same category, ideally from one manufacturer.
Have every permanent link tested with a certification tester, and ask for the test report per outlet. A continuity tester that shows the pairs are wired correctly says nothing about 10 Gbit. What else belongs in the quote:
- The class of the link (E or EA) and the system used to achieve it.
- The fire performance class of the cable. Permanently installed cable falls under the Construction Products Regulation (CPR) and carries a Euroclass. Which class your building needs follows from its fire strategy and local rules.
- Labels at both ends and a patch schedule that is correct at handover.
- Separation from power cables. The installation standard (BS EN 50174 in the UK) sets separation distances between data and power; agree who lays what in the containment.
When fibre instead of copper
Copper stops at a hundred metres per channel. Beyond that, and between the comms cabinets on different floors, fibre is the answer. Between two buildings fibre is almost always better, because it creates no electrical connection between two installations that each have their own earth.
On the floor copper remains the logical choice: devices have an RJ45 port, PoE only runs over copper, and a copper link is easier to change. Which fibre you run between cabinets, singlemode or multimode, is a separate choice with its own pitfalls.
Where our work stops
What we do. We install data cabling: copper and fibre, from patch panel to outlet and between cabinets. We terminate, label, test every link and hand over the test report and patch schedule. We advise on the category and the number of outlets, and we install the switches and access points that connect to it.
What we do not do. We are not an electrical contractor and not a building contractor. Power circuits, building earthing, openings in walls and floors and fire-stopped penetrations belong to the electrician or the contractor, and the fire class the building requires comes from its fire strategy, not from us. We agree with them in advance what is needed so the cables fit through.
Questions we get about this
The five that come up most on a new installation.
Is Cat6a better than Cat6?
For 10 Gbit, yes: Cat6a runs it over the full hundred metres, Cat6 only over a shorter run. For 1 Gbit and for the 2.5 and 5 Gbit of modern access points both are suitable. On a new installation Cat6a is the sensible choice, because the cable outlasts the equipment.
How far can Cat6 run 10 Gbit?
Around fifty-five metres, and even then depending on how tightly the cables are bundled. Cat6a runs 10 Gbit over the full hundred-metre channel. If you need 10 Gbit for certain, install Cat6a and have it tested.
Is Cat7 better than Cat6a?
Not with RJ45 connections. Cat7 was designed for other connectors, and with ordinary RJ45 outlets the link achieves at most Cat6a. Cat7 cable with Cat6a outlets is a perfectly good Cat6a link, but not a step beyond it.
Do I need shielded ethernet cable?
In an ordinary office unshielded Cat6a works well. Shielded makes sense next to lift motors, machinery and heavy electrical plant, and only if the screen runs continuously to the patch panel and is bonded there. Do not mix shielded and unshielded in one system.
Do you also do the wall penetrations and power?
No. We install data cabling, terminate it and test it. Power circuits, earthing, openings in walls and floors and fire-stopped penetrations belong to the electrical contractor or the building contractor. We tell them in advance how many cables need to pass where.
Further reading
Where the cable choice connects.
Shall we talk cabling before the refit?
Send us the floor plan and the number of desks. We will tell you which category and how many outlets we would install, and what the electrician and contractor need to know beforehand.
Practical IT knowledge in your inbox
New guides on management, security and the workplace, written by the people doing the work. No sales talk, and you can unsubscribe in one click.