OM3 vs OM4, and singlemode or multimode: which fibre between floors and buildings

Fibre belongs between the comms cabinets on different floors and between buildings on one site. The question in the quote, OM3 vs OM4 or singlemode instead, decides which speed you can still reach in ten years and which transceivers go in the switch. This is what the difference is and how to choose.

7 min read Written by the ITproposal team
Short answer

Multimode (OM3, OM4) is made for short runs within a building or server room; singlemode (OS2) has practically no distance limit on a site.

How far multimode reaches depends on the speed: the faster, the shorter. If you plan ten years ahead, size for the speed you will need then, not now.

Fibre type, connector and transceiver have to match. You do not connect singlemode straight to multimode.

Singlemode or multimode: the difference is in the core

A fibre consists of a core that carries the light and a 125-micron cladding around it. In multimode the core is 50 microns wide. Light can travel through it along several paths, and those paths are not equally long; over distance the signal spreads as a result. In singlemode the core is about 9 microns, so narrow that the light has only one path.

The consequence is simple. Multimode works with cheaper light sources at 850 nanometres and reaches a few hundred metres, less as the speed goes up. Singlemode uses lasers at 1310 or 1550 nanometres and reaches kilometres, even at high speeds.

Price used to be the argument for multimode: the transceivers were clearly cheaper. That gap has narrowed, while the gap in reach has not. The cable itself is no more expensive in singlemode.

OM3 vs OM4, OM5, and what is already in the wall

Multimode is graded by the bandwidth the fibre achieves. You can often tell them apart by the colour of the jacket:

  • OM1 and OM2 (orange): the older fibres. OM1 even has a different core size, 62.5 microns. If you find it, do not count on it for 10 Gbit.
  • OM3 (aqua): the first fibre optimised for lasers, and for a long time the office standard.
  • OM4 (aqua or violet): the same construction with higher bandwidth, so more reach at the same speed. That is the whole of the OM3 vs OM4 difference.
  • OM5 (lime green): designed to carry several wavelengths at once. Useful in a data centre built around that, rarely on an office floor.

Singlemode is graded OS1a or OS2. OS2 is the usual grade today, indoors and out.

If fibre is already installed, first ask which grade it is and whether it was ever tested. An orange fibre left from an earlier refit decides what speed that link can still carry.

How far you get, per speed

With multimode, distance is not a fixed property of the cable: it depends on the speed you send over it. The Ethernet standard sets a maximum per speed, and that is exactly where OM3 and OM4 differ:

  • 10 Gbit (10GBASE-SR): OM3 up to 300 metres, OM4 up to 400 metres.
  • 25 Gbit (25GBASE-SR): OM3 up to 70 metres, OM4 up to 100 metres.
  • 40 and 100 Gbit over parallel fibres (SR4): OM3 up to 100 and 70 metres, OM4 up to 150 and 100 metres.
  • Singlemode: 10 Gbit and above over 10 kilometres with ordinary LR transceivers.

For an office that means: between the floors of one building OM4 comfortably carries 10 Gbit today. If you want 25 Gbit or more between cabinets in ten years, a hundred metres becomes the limit, and in a larger building or on a site that soon gets in the way.

Which fibre where: between floors, buildings and in the server room

The choice follows from three questions: how long is the link, what speed has to run over it during the life of the building, and what is already there?

  • Between buildings on a site: singlemode. Distances are longer than they look on the plan, because the cable follows the ducts rather than a straight line, and nobody wants to dig twice.
  • A new backbone between floors: singlemode, or OM4 if the distances are short and the rest of the building is already multimode. More and more new buildings get singlemode, because it removes the question of how far the next speed will reach.
  • Inside the server room, rack to rack: multimode is still normal there, and OM4 is the sensible minimum.
  • Existing multimode that works: leave it and test it. Replace it only when the speed you need no longer reaches the distance.

Do not mix fibre types within one link. A singlemode transceiver on multimode fibre, or the reverse, works unreliably or not at all.

Connectors, the transceiver and termination

In offices and server rooms LC duplex is the usual connector: two fibres, one to transmit and one to receive. For 40 and 100 Gbit over multimode, several fibres run through a single MPO connector. Singlemode connectors come in two polishes: flat (UPC, blue) and angled (APC, green). The two do not mate with each other; doing so causes loss and damages the end faces.

The transceiver decides what the link does. It has to match the fibre type, the wavelength and the speed, and the switch: many manufacturers only accept modules coded for their equipment. Put the transceiver type in the same order as the networking equipment, not as a separate line afterwards.

The cable can be terminated in two ways: on site with fusion-spliced pigtails, or pre-terminated with the connectors already fitted. Pre-terminated is quicker to install, but the length must be known exactly in advance and the connectors have to fit through the ducts.

Counting fibres, and the cable between two buildings

Install more fibres than you use today. One link uses two, a second path for resilience another two, and a future speed may call for parallel fibres. Extra fibres in the same cable cost little; pulling a second cable means a new trench or another round through the risers.

Between buildings you need an external-grade cable, made for moisture, temperature and sometimes rodents. A cable with no metal in it keeps the two buildings electrically separate, which is exactly why you use fibre there. If it does have metallic armour, that must be correctly earthed at both ends; that is work for the electrician.

Note the difference with the connection to the outside world. The fibre from the street to the building belongs to the network operator and is a different question from the fibre between your own cabinets and buildings.

Testing and handover

Every fibre link has a loss budget: how much light may be lost along the way before the transceiver can no longer read it. Every connector and every splice costs a little. Handover should therefore include a measurement per fibre:

  • A loss test with a light source and power meter, per fibre and per wavelength, against the budget for the speed you want.
  • An OTDR trace on longer links or links with splices, showing where along the way loss occurs.
  • Connector inspection. Dirt on an end face is the most common cause of a fibre fault, and a speck of dust is invisible to the naked eye.
  • Documentation: which fibre ends on which port of which panel, with type, grade and test result.

Where our work stops

What we do. We install data cabling, including fibre: between the comms cabinets on different floors and between buildings on a site, through the containment, risers and ducts that are in place. We terminate, test every fibre, hand over the test report and patch schedule, and supply and configure the switches and transceivers that connect to it.

What we do not do. We are not a building contractor and not an electrical contractor. Groundworks and underground ducts, openings in walls and floors, fire-stopped penetrations, power and the earthing of an armoured cable belong to the contractor or electrician. We tell them in advance how many cables need to pass where. The fibre in the street belongs to the network operator.

Frequently asked

Questions we get about this

The five that come up most.

What is the difference between OM3 and OM4?

OM4 has a higher bandwidth than OM3, which gives more reach at the same speed. At 10 Gbit that is up to 400 metres against up to 300 metres, at 25 Gbit up to 100 metres against up to 70. Connectors and transceivers are the same, so on a new installation OM4 is the logical minimum.

What is the difference between singlemode and multimode fibre?

The size of the core. Multimode has a 50-micron core and reaches a few hundred metres, less as speed rises. Singlemode has a core of about 9 microns and reaches kilometres, even at high speeds. Within a building either can work; between buildings singlemode is the safe choice.

How far can multimode fibre go?

It depends on the speed. At 10 Gbit OM4 reaches 400 metres, at 25 Gbit 100 metres, and at 40 or 100 Gbit over parallel fibres 150 or 100 metres. If you need to go further or faster later, choose singlemode.

Can singlemode and multimode be connected together?

Not directly. The cores differ too much in size, and a transceiver is made for one or the other. One link should use one fibre type, with transceivers to match.

Do you also dig the trench between two buildings?

No. Groundworks, underground ducts, openings and fire-stopped penetrations belong to the building contractor or electrician. We run the fibre through the ducts in place, terminate it and test it, and tell them in advance what is needed.

Related services

Further reading

Where the fibre choice connects.

Shall we walk through your network backbone?

Send us the floor plan with the comms cabinets and what is installed now. We will tell you which fibre we would run, how many cores, and what the contractor needs to know beforehand.

Practical IT knowledge in your inbox

New guides on management, security and the workplace, written by the people doing the work. No sales talk, and you can unsubscribe in one click.

We use your address for the newsletter only. See our privacy policy.

Request a quote Call